Specific Yield KPI
Description
The Specific Yield KPI quantifies how much AC energy is delivered per unit of installed DC capacity. It provides a normalized metric for evaluating site performance independent of plant size and is especially useful for comparing across projects.
This KPI is calculated daily and expressed in units of kWh/kWp.
Methodology
-
Retrieve time-series data for:
meter_active_power: AC power delivered by the site over the day.
-
Clean and aggregate the data:
- Clip negative values to zero to eliminate erroneous readings.
- Resample data to hourly averages to standardize granularity.
-
Calculate total energy delivered:
- Integrate the hourly AC power measurements to get total daily energy output in kWh.
-
Normalize by DC capacity:
- Divide the total energy output by the site’s installed DC capacity (also referred to as kW-peak, or kWp) to get the specific yield.
-
Compute Specific Yield:
-
The formula is:
-
-
Store the KPI result:
- The resulting value is stored as a project-level KPI for the corresponding date.